Thermal Runaway in VRLA Batteries
It would be very unusual to experience thermal runaway in a properly applied and maintained valve regulated lead acid (VRLA) battery system. However, thermal runaway and its prevention continues to be a serious concern of those using the VRLA battery in float service applications.
Thermal runaway occurs in a VRLA battery when the rate of internal heat generation exceeds the rate at which the heat can be dissipated into the environment. Should this condition continue for an extended period, the VRLA battery temperature could increase until ultimately the cells will dry-out and the container, if plastic, may soften (100¡ãC), rupture and melt (160¡ãC).
Oxygen Recombination Cycle
During charging of the VRLA battery some heat is generated internally due to charging current flowing through the resistive components of the cells (l2Ri). However, the major portion of the internal heating results from the exothermic reaction at the negative plate where the oxygen gas (O2) from the positive plate reacts with the lead (Pb) and sulfuric acid (H2SO4) to form lead sulfate (PbSO4) and water (H2O) as noted in equations 2 and 3 below. Approximately 90% of the current supplied to the battery during float charging is used to facilitate this oxygen recombination cycle.

This oxygen recombination cycle is negligible in the free liquid electrolyte (vented) cell because the oxygen gas generated at the positive plate is free to percolate up through the electrolyte to the environment rather then being redirected by an AGM separator or gel to diffuse to the negative plate. Consequently the "vented" liquid electrolyte lead acid cell does not exhibit oxygen recombination thus it emits oxygen and hydrogen at low float voltage, draws less float current and generates less heat than does a VRLA cell.


The difference in the float current acceptance of the vented (liquid electrolyte) cell and the gelled and AGM VRLA cell is shown in Figure 3. As would be suspected, the AGM VRLA battery, with the most efficient recombination cycle, has the greatest float current. Consequently, it is also the most susceptible to thermal runaway since it is the more effective heat generator .

Float Current and Temperature
Also note in Figure 3 that at a constant float charging voltage (e.g. 2.30 v/c), the float current will rise with any increase in battery temperature. This increase in current is primarily in response to the increased rate of oxygen generation at the positive plate and resulting increase in the recombination rate at the negative plate. As you would suspect, the increased rate of oxygen recombination will increase the rate of heat generation and result in a further increase of the battery temperature unless the heat can be effectively dissipated.
Float Current and Voltage
The float current is also a function of the float voltage as shown in Figure 4 where the vented and gelled electrolyte and AGM VRLA battery float currents are compared at 2.25, 2.30 and 2.40 volts per cell. As would be suspected, the higher charging voltage will result in increased oxygen generation at the positive plate and recombination at the negative plate, resulting in increased float current and heat generation within the battery. Again, this increase in float charging voltage and resulting increase in float current will result in an increase of battery temperature unless the heat generated is effectively dissipated.

Float Voltage and Gassing
As the float voltage applied to the battery is increased, the oxygen generation rate at the positive plate will increase. At some point between 2.35 and 2.40 volts per cell the oxygen gas generation rate at the positive plate will be greater than the rate at which it can diffuse through the gel and/or AGM separator medium to the negative plate. At this point, as shown in Figure 5, the VRLA battery gassing will increase dramatically and approach that of the vented liquid electrolyte cell. This gassing will eventually result in dry-out of the electrolyte. As water is lost from the electrolyte it will increase the void space between the positive and negative plate. This increased void space will provide for improved diffusion of oxygen gas to the negative plate and an increase in the recombination efficiency resulting in additional heating.

Conditions Conducive to Thermal Runaway
The conditions conducive to thermal runaway are those which either singly or in combination significantly increase the heat generated within the battery or minimize its ability to dissipate the internally generated heat to the environment. These would include:
1. Too high of float charging voltage which results in;
a. elevated float charging current
b. accelerated gassing and dryout
c. increased oxygen recombination rate and resulting heating
2. Too high of "recharge" current resulting in an increase of 10¡ãC (18¡ãF) in the battery temperature above the ambient temperature.
3. Repetitive high-rate discharge - recharge cycling of the battery resulting in a long-term excessive temperature rise above the ambient temperature.
4. High temperature operating environment which results in:
a. decreased temperature differential and ability of the battery to dissipate internally generated heat
b. increased plate grid corrosion rate
c. increased float current acceptance
d. accelerated gassing and dryout
e. increased oxygen recombination rate and heating
5. Improper enclosure design or battery installation resulting in a high temperature operating environment or inability of the battery to dissipate heat via convection and radiant techniques. These items would include:
a. enclosure located in direct sun
b. enclosure painted dark color
c. enclosure lacks adequate ventilation
d. batteries mounted "side to side" and lack appropriate spacing which allows for convection airflow and radiant heat dissipation.
6. System or battery failures resulting in the above conditions, such as;
a. ground faults
b. shorted cells
c. charger high voltage (loss of regulation) output
d. charger excessive AC ripple voltage / current output
e. loss of enclosure cooling / ventilation capability
Float Charging Voltage @ 25¡ãC (77¡ãF) and Higher
Elevated charging voltage will certainly reduce the recharge time required following discharge however, if applied during the float phase it will force increased oxygen gas generation, increased float current acceptance, gassing and heating. Since water lost cannot be replaced in a VRLA battery, this gassing and resulting water loss will result in reduced capacity and service life. This is in addition to the resulting increased void space between the plates allowing for increased diffusion rate of oxygen to the negative plate; increased efficiency of the oxygen recombination cycle and increased heat generation.
The VRLA battery should be able to withstand an indefinite period of charging at 2.40 volts per cell without entering thermal runaway even though the battery will eventually dry out and prematurely fail for other reasons. However, should the battery be continuously charged at above 2.50 volts per cell, either due to an incorrectly set charger or shorted cells within the string, it can be assumed that the battery will eventually enter into a thermal runaway condition.
The charging voltage utilized under normal environmental conditions (77¡ãF / 25¡ãC) should be as noted in Table 1 for best performance of the CCB VRLA batteries and avoidance of thermal runaway.
|
Dynasty Series
|
Electrolyte
Immobillzation
Technique |
Electrolyte
Speclfle Gravlty |
Recommended
Average
Float Voltage
@25¡æ |
Recommended
Average
Cycle Service/Equaflzattion
Voltage@25¡æ |
|
GC |
Gel |
1.300 |
2.25 ¡ª 2.30 v/c |
2.40 v/c |
|
BBG |
Gel |
1.300 |
2.25 ¡ª 2.30 v/c |
2.40 v/c |
|
BBA |
AGM |
1.300 |
2.25 ¡ª 2.30 v/c |
2.40 v/c |
|
DCS* |
AGM |
1.300 |
2.25 ¡ª 2.30 v/c |
2.40 ¡ª 2.48 v/c |
|
MPS |
AGM |
1.300 |
2.25 ¡ª 2.30 v/c |
2.40 v/c |
|
UPS |
AGM |
1.300 |
2.25 ¡ª 2.30 v/c |
2.40 v/c |
|
TEL |
AGM |
1.300 |
2.25 ¡ª 2.30 v/c |
2.40 v/c |
*Intended for deep cycie service
Table 1 £ Recommended Charging Voltages at 25¡æ
As shown previously in Figure 3, as the temperature rises the float current will rise (at a fixed voltage) and this increase in float current will eventually be evidenced in the increased emission of gas from the cell as shown in Figure 6. Again, this will lead to accelerated dry-out of the electrolyte, increased void space between the plates and increased oxygen recombination and heating within the cell leading to thermal runaway.

When it is anticipated that the battery will be subjected to elevated temperatures (greater than 92¡ãF) during continuous float charging, the charging voltage should be reduced so as to minimize the oxygen gas generation, current acceptance, gas emission, heating and potential for thermal runaway of the battery. The temperature compensation factor to be used should be between -0.002v/c per ¡ãF and -0.003v/c per ¡ãF. Figure 7 illustrates a temperature compensation factor of -0.0028v/c per ¡ãF.

Unlimited Recharging Current
During recharge of the VRLA battery there is heating due to the l2R losses in the cell in addition to the normal exothermic oxygen recombination reaction occurring at the negative plate. Since the heating is proportional to the square of the current acceptance, excessive recharging current for an extended period, as with repetitive cycles, will have a pronounced heating affect on the cell. The magnitude and duration of the current accepted by the battery during the bulk phase of the recharge is directly related to the depth of the previous discharge and the current available from the charger. To limit the temperature rise of the battery to less than 10¡ãC during the recharge, the available charging current allowed should be a function of the previous depth of discharge and limited to the maximum values noted in Table 2.

High Temperature Operating Environments
Battery float charging in a hot environment is the most common cause of thermal runaway. As shown previously in Figure 3 as the temperature of the battery increases the rate of oxygen recombination and float current acceptance will increase thus causing the battery temperature to further increase - and so the cycle goes. Naturally, when the battery is charged in a "hot" environment it will not be able to efficiently dissipate the heat that is internally generated. Thus it is important to minimize the heat generated through temperature compensation of the charging voltage or removal of the charging voltage when the battery temperature exceeds 122¡ãF (50¡ãC) or is 18¡ãF (10¡ãC) above the ambient temperature.
Situations that lead to high temperature operating environments include:
1. Installation in hot environments such as boiler rooms, foundries, metal enclosures exposed to direct radiation of the sun, etc.
2. Installation in unventilated enclosures
3. Installation of batteries without adequate spacing between the units
4. Installation of batteries above or adjacent to heat producing components
Battery Failures Resulting in Thermal Runaway
A ground fault can induce excessive current and heating in a portion of a battery string and result in thermal runaway. Although there is no free liquid electrolyte to flow from a broken container, should there be a crack in the lower container, capillary action can result in a slight film of conductive electrolyte forming in and about the crack. Should this electrolyte film be in contact with an un-insulated metal component that is common to either polarity of the battery an excessive short circuit current can result. This "ground fault" current could result in thermal runaway of a portion of the string or even a fire.

Continuing to charge a string of cells when one or more of the cells exhibit internal shorts, can result in thermal runaway. For example, assume a string of 12 cells is being charged at 27.6 vdc (2.30 v/c) and the string continues in operation with one of the cells shorted. In this situation the average charging voltage on the remaining 11 good cells is 2.5 v/c. While this may not result in immediate thermal runaway, assume that 2 cells were shorted resulting in an average charging voltage of 2.76 v/c on the remaining 10 cells. This will certainly result in very high float current and near term thermal runaway.

Potential causes of shorted cells include:
1. neglect in the discharged condition
2. long term storage without a freshening charge
3. continuous undercharging resulting in sulfated plates
4. continued operation beyond a reasonable life expectation
5. mechanical damage resulting in a bent plate
System Failures Resulting in Thermal Runaway
The most obvious of system failures that could result in thermal runaway is failure of the charger in the over-voltage condition.
A somewhat less obvious but equally detrimental failure would be that of the output filtering of the battery float charger. Even though the AC ripple voltage output of the charger may be quite low (less than 0.5%rms of the float voltage), the internal resistance of the battery being charged can be extremely low and a significant AC ripple current will flow through the battery. The AC ripple current from the charger could be several amperes and can cause additional heating of the battery in accordance with I2R.
An AC ripple voltage of only 0.3%rms (0.04 Vrms per 12-volt block) is illustrated in Figure 10. Assuming this was applied to a 100Ah battery with an internal resistance of 0.0025 ohms, it would result in an AC ripple current of 16.2 amperes rms (i = e/r). This is a considerable current and would result in additional heating of the battery equivalent to 0.656 watts / block (l2Ri) or 2.24 BTU per hour (watts X 3.4134 BTU/watt) per 12 volt block.

If the AC ripple output voltage of the charger exceeds 4% peak to peak of the float voltage, as shown in Figure 11, this could result in actual "cycling" of the battery and a resulting additional rapid rise in temperature, DC float current, gassing etc.
To prevent heating of the battery due to AC ripple current, the AC ripple current should be limited to less than 5 amperes rms per 100 Ah of rated battery capacity.
Instantaneous Float Voltage with 4.8% p-p ripple

Naturally when a mechanical ventilation or cooling system is utilized to maintain an acceptable environment for the battery, any failure or interrupted service of that system can result in elevated operating temperatures and eventual accumulation of an explosive mixture of hydrogen gas with the expected results.
Prevention and Detection of Thermal Runaway
While thermal runaway can be a catastrophic failure of the battery system, proper application and system design, installation and operation can render it a non-issue. A summary of the potential causes of thermal runaway and appropriate preventative measures are noted in Table 3.
|
Potential Cause |
Prevention |
Detection |
Immediate Action |
|
|
High Float Charging Voltage |
Set to manufacturer recommendation for temperature of operation
Temperature compensated charging voltage |
Charger high - voltage alarm
Battery high- temperature alarm |
Interrupt charger output to battery |
|
|
|
High Recharge Current Availability |
Reduce charger output capability or increase battery Ah capacity |
Alarm on 10¡ãC temperature difference between battery and environment |
Interrupt charger output to battery |
|
|
High Temperature Operating Environment |
Install in cool area
Install with 0.5" spacing
Install in ventilated space (natural or mechanical)
Reflective paint and situate enclosure to avoid radiant heat sources
Install active or passive cooling system |
Battery high temperature alarm
Enclosure high temperature alarm
|
Interrupt charger output to battery |
|
|
Ground Faults |
Observe battery containers for damage during installation |
Ground Fault Detector/Monitor
Float current monitor |
Interrupt charger output to battery |
|
|
Shorted Cells |
Maintain "fresh" inventory
Recharge within 24 hours of discharge
Charge @ recommended voltage
Perform recommended PM
Perform periodic capacity test |
OCV greater than 2.08 v/c
Manual or automatic monitoring
Less than 80% rated Ah capacity |
Apply freshening charge
Set charger output voltage to recommended value for operation temperature Replace battery |
|
|
Charger excessive AC ripple voltage/current |
Increase charger output filtering |
Manually or automatically monitor
Battery temperature 10¡ãC above ambient
|
Replace charger output filters
Interrupt charger output to battery |
|
Table 3 - Thermal Runaway Detection and Prevention
Should severe thermal runaway occur, it will be evidenced by permanent container distortion due to the heat and eventual emission of trace amounts of hydrogen sulfide gas (rotten egg odor) as the electrolyte is completely gassed off. Should this situation be encountered, the charging voltage to the battery should be immediately removed to stop the thermal runaway reactions and the area should be ventilated. When thermal runaway has occurred, the damage to the battery is permanent and it must be replaced.